Air-water Cooled Transformer
Air-water Cooled Transformer

Air-water Cooled Transformer

CS(G)D, CSCD series air-water cooled medium-voltage transformers, the transformer body is placed in a sealed enclosure, and the heat generated by the transformer during operation is carried out of the enclosure by air-water cooling devices to ensure the long-term stable operation of the transformer.
Send Inquiry

Product Features

 

CS(G)D, CSCD series air-water cooled medium-voltage transformers, the transformer body is placed in a sealed enclosure, and the heat generated by the transformer during operation is carried out of the enclosure by air-water cooling devices to ensure the long-term stable operation of the transformer.

 

This product is suitable for ships, offshore platforms, various key projects, urban power grid construction and various special environments, and is widely used in airports, shipyards, docks, power plants, stations, industrial and mining enterprises, power communication, scientific research institutions, high-rise buildings, residential communities, business centers and other places.

 

Technical Parameters

 

Model

Rated capacity

(kVA)

Rated frequency

Primary voltage

(V)

Secondary voltage

(V)

Connection group

No-load current

(%)

No-load loss

(W)

Load loss 110 °C

(W)

Short-circuit impedance

(%)

CS(G)D

CSCD

30

50Hz

or

60Hz

3

3.3

6.3

6.6

10

10.5

11

Or other

0.4

0.45

0.69

Or other

Yy0

Dd0

Yd11

Dy11

2.4

220

750

4.0

40

2.4

265

900

50

2.4

310

1060

63

2.4

355

1205

80

1.8

420

1460

100

1.8

450

1670

125

1.6

530

1960

160

1.6

610

2250

200

1.4

700

2680

250

1.4

810

2920

315

1.2

990

3670

400

1.2

1100

4220

500

1.2

1310

5170

630

1.0

1510

6220

800

1.0

1710

7360

6.0

1000

1.0

1990

8160

1250

1.0

2350

10215

1600

1.0

2800

12410

2000

0.8

3800

15270

2500

0.8

4600

18135

3150

0.8

5500

22060

4000

0.8

6300

26515

5000

0.6

7400

31290

6300

0.6

8600

37225

Note: Specific capacity is not listed in the table and can be customized according to customer requirements. The data in the table may be changed without further notice, subject to the product's factory release

 

Product Advantages

 

High heat dissipation performance

The air-water cooled transformer achieves higher heat dissipation efficiency than a single cooling method through a dual synergy mechanism of direct core heat absorption by the water cooling system (taking advantage of the high specific heat capacity of water for rapid heat conduction) and enhanced heat dissipation by the air cooling system (forced ventilation for accelerated heat dissipation), especially suitable for high-temperature and high-load scenarios above 180°C (such as ship power, new energy power stations). It effectively suppresses insulation aging and ensures stable operation of the equipment.

 

Compact structure and high reliability

The air-water cooled transformer achieves a volume reduction of over 30% compared to traditional oil-immersed transformers through modular cabinet design (such as a closed frame box body + top cooling radiator layout). At the same time, it adopts a fully sealed anti-corrosion structure (titanium heat exchanger, three-proof motor) and seismic redundancy design, significantly enhancing stability in harsh environments such as ship turbulence and high humidity salt spray.

 

Energy efficiency and economic benefits

The energy efficiency is reflected in the dual cooling synergies: the water cooling system directly recovers more than 70% of the waste heat (such as recycling boiler feed water), and the air cooling system dynamically reduces energy consumption through variable-frequency fans, with the overall energy consumption reduced by 15% to 30% compared to a single air cooling system; The economic benefits come from oil-free line maintenance (eliminating the cost of oil change) and low failure rate design (only fans/pumps are vulnerable parts), reducing operation and maintenance costs by 50%.

 

Hot Tags: air-water cooled transformer, China air-water cooled transformer, Dry Type Transformer with Water Air Cooling, Flameproof Mining Transformer, Hybrid Cooling Transformer, Medium Frequency Transformer, Mining Transformer, Phase Angle Regulating Transformer